Seitenansicht 50
1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Bottom display: circuit 2:
Evaporator 2 water outlet, with the label OuT2.
Par. dP03 = 2
Top display of the circuit 1:
Condenser 1 water inlet temperature with the label CIn1
Bottom display of the circuit 1
Condenser 1water outlet with the label COu1.
Top display of the circuit 2:
Condenser 2 water inlet temperature with the label Cin2
Bottom display of the circuit 2
Condenser 2water outlet with the label Cou2.
Par. dP03 = 3
Top display of the circuit 1:
Condenser probe temperature Cdt1 / pressure CdP1
Bottom display of the circuit 1
Evaporator pressure probe LP1
Top display of the circuit 2:
Condenser probe temperature Cdt2 / pressure CdP2
Bottom display of the circuit 2
Evaporator pressure probe LP2
15.4 DEFAULT DISPLAY READ - OUT OF THE REMOTE PANELS VI620S AND VI820S
If the parameter dP04 = 0 the upper display of the remote panels #1 and #2 depends on the parameter values dP01 – dP02 – dP03; to
show the temperature detected by the internal probe of the remote panel accessing the function menu under the function trEm.
If the parameter dP04 = 1 the upper display of the remote panels #1 and #2 show their internal NTC sensor (ambient temperature); to
show the same temperature it is possible to eccess the function menu under the function trEm.
15.5 DEFAULT DISPLAY READ - OUT OF THE REMOTE PANELS VI620S AND VI820S
If the parameter dP04 = 0 the upper display of the remote panels #1 and #2 depends on the parameter values dP01 – dP02 – dP03; to
show the temperature detected by the internal probe of the remote panel accessing the function menu under the function trEm.
If the parameter dP04 = 1 the upper display of the remote panels #1 and #2 show their internal NTC sensor (ambient temperature); to
show the same temperature it is possible to eccess the function menu under the function trEm.
16 DISPLAY INFORMATION
16.1 SHOW THE SET POINT VALUE
Push and release the SET key, the leds of the circuits are off and the set value is displayed.
In stand-by the bottom display shows SetC (set chiller), by pushing SET again the next label is SetH (set heat pump ).
If the unit is running the only set displayed is related to the running mode.
16.2 MODIFY THE SET POINT
1) Push SET key for at least 3 seconds: the leds of the circuits are off and the set value is blinking.
2) Use the UP or DOWN key to modify the setpoint.
3) Push SET to confirm or wait the timeout (15seconds).
16.3 SHOW THE ACTIVE SETPOINT DURING ENERGY SAVING OR DYNAMIC SETPOINT
If the unit is running in chiller or HP, the Energy Saving or the Dinamic Setpoint activity is signalled by the blinking led of the SET button.
Chiller mode: push SET one time, the bottom display shows the SEtC (set chiller) while the top display shows the set value. Only if the
Energy saving or the Dynamic Setpoint are active, pushing another time the SET key, the bottom display shows “SEtr” (real setpoint),
and the top display shows the setpoint that the unit is really using for the thermoregulation.
Chiller mode: push SET one time, the bottom display shows the SEtH (set Heat pump) while the top display shows the set value. Only
if the Energy saving or the Dynamic Setpoint are active, pushing another time the SET key, the bottom display shows “SEtr” (real
setpoint), and the top diplay shows the setpoint that the unit is really using for the thermoregulation.
ATTENTION
The SEtr label appears only if the Energy saving or the Dynamic Setpoint are active.
To modify the working setpoint it is necessary the setpoint values is displayed on both the display (temperature / temperature or
temperature / pressure o pressure/ pressure) without any identification label, otherwise the SET key swaps to the circuit information.