1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pg.34/106
CO 20 Time to make run the pumps together before rotating from one to the other
(See water pump group function)
0 250 Sec
Condenser water pump
CO 21 Operative mode for condenser water pump (See condenser water pump
function)
0= Not enabled.
1= Continuous. When the unit is running in Chiller or HP the is running.
2= With compressor. When a compressor is running also the pump is running.
0 2
CO 22 Free
CO 23 OFF delay condenser water pump after compressor switching OFF. This
delay is also active when the unit is turned in stand-by (See evaporator water
pump function).
0 250 Min
CO 24 Number of time running hours for pump rotation (See water pump group
function).
0 999 10Hr 10Hr
CO 25 Time to make run the pumps together before rotating from one to the other
(See water pump group function).
0 250 Sec
Load maintenance
CO 26 Compressor 1 hour counter set (See maintenance request) 0 999 10 Hr 10 Hr
CO 27 Compressor 2 hour counter set (See maintenance request) 0 999 10 Hr 10 Hr
CO 28 Compressor 3 hour counter set (See maintenance request) 0 999 10 Hr 10 Hr
CO 29 Compressor 4 hour counter set (See maintenance request) 0 999 10 Hr 10 Hr
CO 30 Compressor 5 hour counter set (See maintenance request) 0 999 10 Hr 10 Hr
CO 31 Compressor 6 hour counter set (See maintenance request) 0 999 10 Hr 10 Hr
CO 32 “Evaporator pump / Supply fan” hour counter set (See maintenance request) 0 999 10 Hr 10 Hr
CO 33 2
nd
Evaporator pump hour counter set (See maintenance request) 0 999 10 Hr 10 Hr
CO 34 Condenser pump hour counter set (See maintenance request) 0 999 10 Hr 10 Hr
CO 35 2
nd
Condenser pump hour counter set (See maintenance request) 0 999 10 Hr 10 Hr
Pump down
CO 36 Pump down operating mode (See pump down ON/OFF function)
0= Not enabled
1= Unit off with pump–down, unit on without pump–down
2= Unit off with pump–down, unit on with pump–down
3= Chiller mode off with pump–down, chiller mode on without pump–down
4= Chiller mode off with pump–down, chiller mode on with pump–down
0 4
CO 37 Pump–down pressure setpoint (See pump down ON/OFF function) 0
0
50.0
725
Bar
psi
Dec
int
CO 38 Pump-down pressure differential (See pump down ON/OFF function) 0
0
14.0
203
Bar
psi
Dec
int
CO 39 Maximum pump–down time duration at start-up and stop (See pump down
ON/OFF function)
0 250 Sec
Evaporator Unloading
CO 40 Unloading compressor setpoint in chiller. From high temperature of the
evaporator water inlet (See unloading function).
-30
0
70.0
725
°C
°F
Dec
int
CO 41 Unloading Differential. From high temperature of the evaporator water inlet
(See unloading function).
0.0
0
25.0
45
°C
°F
Dec
int
CO 42 Delay time to engage the Unloading function from high temperature of the
evaporator water inlet (See unloading function).
0 250 Sec 10sec
CO 43 Maximum unloading duration time to keep activated the Unloading function
from high temperature of the evaporator water inlet (See unloading function).
0 250 Min
Condenser Unloading
CO 44 Unloading compressor setpoint. From temperature / pressure in chiller mode
(See unloading function).
0
0
50.0
725
Bar
psi
Dec
int
CO 45 Unloading Differential. From temperature / pressure in chiller mode (See
unloading function).
0.0
0
14.0
203
Bar
Psi
Dec
int
CO 46 Unloading compressor setpoint. From temperature / pressure in HP mode
(See unloading function).
0
0
50.0
725
Bar
psi
Dec
int
CO 47 Unloading Differential. From temperature / pressure in HP mode (See
unloading function).
0.0
0
14.0
203
Bar
Psi
Dec
int
CO 48 Maximum unloading duration time from temperature/pressure control. 0 250 Min
CO 49 Number of steps for circuit with active unloading
1= 1
st
step
2= 2
nd
step
3= 3
rd
step
1 3
CO 50 Minimum ON time of the capacity step after the unloading function start (only
for capacity compressor)
0 250 Sec
Compressor liquid injection
CO 51 Setpoint of the solenoid valve (on) of the liquid injection 0
0
150
302
°C
°F
Dec / int
int
CO 52 Setpoint of the solenoid valve (off) of the liquid injection 0.0
0
25.0
45
°C
°F
Dec
int
Pr1 Password 0 999
Pr2 Password 0 999
Pr3 Password 0 999