1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pg.36/106
FA 10
Proportional speed control FA01 = 4
Temperature or pressure limit to enable the maximum speed FA 8
ON/OFF regulation FA01 = 2/3
SETpoint step n° 2
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 11 Proportional speed control FA01 = 4
Proportional band for condenser fan control in chiller
To set the temperature/pressure differential between the minimum and the
maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 1
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 12 Proportional speed control FA01 = 4
CUT-OFF differential in chiller. To set a temperature/pressure differential to
stop the fan.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 2
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 13 Over ride CUT- OFF in chiller. To set a temperature/pressure differential to
keep the minimum fan speed.
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 14 CUT-OFF time delay. To set a time delay before activating the CUT-OFF
function after the fan start-up.
If after the compressor start-up the proportional regulator requires to turn off
the fan (cut-off) and FA140, the fan is on at the minimum speed for the time
set in this parameter. If FA14=0 the function is disabled.
0 250 Sec
FA 15 Night speed in chiller. To set the maximum fan speed percentage value
(30..100%), it is related to the fan power supply.
30 100 %
Fan in Heat pump mode
FA 16 Minimum speed for condenser fan in Heat Pump mode.
To set the minimum fan speed percentage value (30..100%), it is related to
the fan power supply.
30 100 %
FA 17 Maximum speed for condenser fan in Heat Pump mode.
To set the maximum fan speed percentage value (30..100%), it is related to
the fan power supply.
30 100 %
FA 18 Proportional speed control FA01 = 4
Temperature or pressure limit to enable the minimum speed FA16
ON/OFF regulation FA01 = 2/3
SETpoint step n° 1
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 19 Proportional speed control FA01 = 4
Temperature or pressure limit to enable the maximum speed FA17
ON/OFF regulation FA01 = 2/3
SETpoint step n° 2
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 20 Proportional speed control FA01 = 4
Proportional band for condenser fan control in heat pump
To set the temperature/pressure differential between the minimum and the
maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 1
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 21 Proportional speed control FA01 = 4
CUT-OFF differential in heat pump. To set a temperature/pressure differential
to stop the fan.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 2
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 22 Over ride CUT- OFF in Heat pump. To set a temperature/pressure differential
to keep the minimum fan speed.
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 23 Night speed in Heat pump. To set the maximum fan speed percentage value
(30..100%), it is related to the fan power supply.
30 100 %
Hot start
FA 24 Hot start setpoint -30.0
-22
70.0
158
°C
°F
Dec
int
FA 25 Hot start differential 0.0
0
25.0
45
°C
°F
Dec
int
3 / 4 step condenser Fan in Chiller mode
FA 26 ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 27 ON/OFF regulation FA01 = 2/3
SETpoint step n° 4
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
3 / 4 step condenser Fan in heat pump