1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
FA 28 ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 29 ON/OFF regulation FA01 = 2/3
SETpoint step n° 4
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
Pr1 Password 0 999
Pr2 Password 0 999
Pr3 Password 0 999
Antifreeze heaters – Integration heating - boiler
Parameter Description min max m. u. Risoluzione
Ar 1 Anti-freeze heaters/integration heating setpoint for air/air unit in Chiller mode.
To set a temperature value, below this value the anti-freeze relay is activated.
-30.0
-22
70.0
158
°C
°F
Dec
int
Ar 2 Regulation band for antifreeze in Chiller mode.
0.1
0
25.0
45
°C
°F
Dec
Int
Ar 3 Set Anti-freeze heaters/integration heating setpoint for air/air unit in HP mode.
To set a temperature value, below this value the anti-freeze relay is activated.
-30.0
-22
70.0
158
°C
°F
Dec
int
Ar 4 Regulation band for antifreeze in HP mode. -30.0
-22
70.0
158
°C
°F
Dec
int
Ar 5 Antifreeze heaters / integration heating in defrost
0= ON only with thermoregulation control
1= ON with thermoregulation and during the defrosting cycle
0 1
Ar 6 Antifreeze alarm probe / heaters / appoggio in Chiller mode.
0= Not enabled
1= Evaporator inlet
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
0 3
Ar 7 Antifreeze alarm probe / heaters / support heaters in HP mode.
0= Not enabled
1= Evaporator inlet.
2= Evaporator outlet 1 and 2.
3= Evaporator outlet 1 and 2 and common outlet.
0 3
Ar 8 Thermoregulation probe for anti-freeze alarm / condenser heaters.
0= not enabled.
1= Condenser common water inlet probe.
2= Condenser common water inlet and condenser inlet 1 / 2 probe.
3= Condenser water outlet 1 / 2 probe.
4= Condenser water outlet 1 / 2 and common outlet.
0 4
Ar 9 Anti-freeze heaters or condenser/evaporator water pump control with unit in
remote OFF or stand-by mode:
0= Control not enable
1=Controlled by anti-freeze thermoregulation.
0 1
Ar 10 Anti-freeze heaters control for condenser/evaporator faulty probe:
0= Anti-freeze heaters OFF
1= Anti-freeze heaters ON
0 1
Boiler function
Ar 11 Boiler function
0=Not enabled
1=Enabled for integration heating
2= Enabled for heating
0 2
Ar 12 External air temperaure setpoint for boiler heaters (on) -30.0
-22
70.0
158
°C
°F
Dec
int
Ar 13 Temperature differential for boiler heaters (off) 0
0
25.0
45
°C
°F
Dec
int
Ar 14 Time delay before turning the boiler on 0 250 Min
Boiler function in Chiller mode
Ar 15 Setpoint for boiler heaters (on) in chiller -30.0
-22
70.0
158
°C
°F
Dec
int
Ar 16 Proportional band for boiler heaters in chiller -30.0
-22
70.0
158
°C
°F
Dec
int
Boiler function in heat pump
Ar 17 Setpoint for boiler heaters (on) in HP -30.0
-22
70.0
158
°C
°F
Dec
int
Ar 18 Proportional band for boiler heaters in HP 0.1
0
25.0
45
°C
°F
Dec
int
Ar 19 External air setpoint to stop the compressor as integration function -30.0
-22
70.0
158
°C
°F
Dec
int
Ar 20 External air differential to stop the compressor as integration function 0.1
0
25.0
45
°C
°F
Dec
int
Pr1 Password 0 999
Pr2 Password 0 999