1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pg.46/106
12 SELECTION AND START OF THE RUNNING MODE
12.1 SELECT THE CHILLER OR THE HEAT PUMP MODE
The CF79 parameter allows to select and enable the running mode:
Par. CF79 = 0: Through keyboard, the user can start and stop the unit using the keys of the front panel.
Par. CF79 = 1: Through digital input programmed to start/stop the unit from remote control.
This selection is enabled if there is one digital input configured as start/stop from remote (remote chiller / heat pump). I non of
the digital input are configure the unit remains in stand–by.
The “open” status of the input forces the chiller running mode.
The “closed” status of the input forces the heat pump running mode.
The keyboard selection is disabled.
The key on the front panel can start/stop the unit only with the digital input selection
Par. CF79 =2: Automatic selection of the Chiller - Heat Pump through analogue input
The analogue input selection or change over function overrides the digital input C-HP function. If the external air temperature are within
the CF81 differential, the user can change the running mode from the keyboard.
If the unit is running with CF79 = 1 or CF79=2, and it is requested a running mode change, the controller turns off all the outputs, starts
a fixed delay time signalled by the chiller or heat pump blinking led. This blinking led indicates which running mode will be activated after
the compressor delay time protection.
12.2 CHANGE OVER
To change the running status the following condition must be respected otherwise the unit remains in stand - by:
1. CF02=1 (heat pump selected)
2. CF79=2 and a NTC probe configured as NTC external air temperature for dynamic setpoint/ boiler / change over
3. This probe is working properly.
Parameters involved with the change over function:
CF80 Change over Setpoint. If the analogue input control (from probe) function is enabled, it represents the limit temperature of the
probe value under which the unit runs the Heat Pump mode.
CF81 Change over Differential. If the analogue input control (from probe) function is enabled, it represents the limit differential
temperature of the probe value to restart in the Chiller mode.
For external air temperature within CF81 the user can manually change the status from keyboard.
GRAPH: AUTOMATIC CHANGE OVER
12.3 CHILLER HEAT PUMP FUNCTIONING MODE
IT IS DEFINED BY THE PARAMETER CF78.
12.4 KEYBOARD SELECTION
CF78 = 0: pushing key the unit starts in chiller, pushing key the unit starts in heat pump
CF78 = 1: pushing
key the unit starts in heat pump, pushing key the unit starts in chiller
12.5 ANALOG INPUT SELECTION
CF78 = 0 NTC, External air temperature probe > CF80+ CF81 the unit starts in chiller, NTC, External air temperature probe < CF80
the unit starts in heat pump.
CF78 = 1 NTC, External air temperature probe > CF80+ CF81
the unit starts in chiller, NTC, External air temperature probe < CF80
the unit starts in heat pump.