1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
23. Temperature probe NTC for auxiliary output #2
24. Temperature probe NTC for condensing circuit #1
25. Temperature probe NTC for condensing circuit #22
After the number 25 the display configuration can be selected from o 1 to c62 that allows to set an analogue input as digital input (see
polarity of the digital input/outputs).
8.2 ANALOG INPUT CONFIGURATION PB3 - PB4 - PB5 - PB6
Parameter involved:
CF10 = Configuration PB3
CF11 = Configuration PB4
CF12 = Configuration PB5
CF13 = Configuration PB6
0 Not enabled
1 Temperature probe PTC for compressor 1 discharge
2 Temperature probe PTC for compressor 2 discharge
3 Temperature probe PTC for compressor 3 discharge
4 Temperature probe PTC for compressor 4 discharge
5 Temperature probe PTC for compressor 5 discharge
6 Temperature probe PTC for compressor 6 discharge
7 Temperature probe NTC for evaporator inlet
8 Temperature probe NTC for evaporator outlet # 1
9 Temperature probe NTC for evaporator outlet # 2
10 Temperature probe NTC for common evaporator outlet
11 Temperature probe NTC for common hot water condenser / recovery inlet
12 Temperature probe NTC for hot water condenser / recovery inlet circuit #1
13 Temperature probe NTC for hot water condenser / recovery inlet circuit #2
14 Temperature probe NTC for hot water condenser / recovery outlet circuit #1
15 Temperature probe NTC for hot water condenser / recovery outlet circuit #2
16 Temperature probe NTC for hot water condenser / recovery common outlet circuit
17 Temperature probe NTC for free cooling water inlet
18 Temperature probe NTC for free cooling external air
19 Temperature probe NTC for external air dynamic setpoint/ boiler / change over
20 Temperature probe NTC for combined defrost circuit #1
21 Temperature probe NTC for free cooling water inlet #2
22 Temperature probe NTC for auxiliary output #1
23 Temperature probe NTC for auxiliary output #2
24 Condenser probe circuit 1 ( temperature NTC / pressure 4÷20 mA / ratio-metric 0÷ 5Volt )
25 Condenser probe circuit 2 ( temperature NTC / pressure 4÷20 mA / ratio-metric 0÷ 5Volt )
26 Evaporator pressure probe circuit 1 (pressure 4÷20 mA / ratio-metric 0÷ 5Volt )
27 Evaporator pressure probe circuit 1 (pressure 4÷20 mA / ratio-metric 0÷ 5Volt )
28 Auxiliary output 1 pressure probe control (4÷20 mA / ratio-metric 0÷ 5Volt).
29 Auxiliary output 2 pressure probe control (4÷20 mA / ratio-metric 0÷ 5Volt).
30 Dynamic setpoint pressure probe (4÷20 mA)
After the number 30 the display read-out goes from “o 1” to “c62” that allows to set an analogue input as digital input (see polarity input
of digital inputs).
8.3 DIGITAL INPUT CONFIGURATION ID1 ID18
Parameters involved:
CF36 = Configuration ID1…CF53 = Configuration ID18
0. Not enabled
1. Remote ON / OFF
2. Remote chiller / heat pump
3. Flow switch/ Supply fan overload
4. Flow switch of heated side
5. Antifreeze heater circuit 1
6. Antifreeze heater circuit 2
7. High pressure switch circuit # 1
8. High pressure switch circuit 2
9. Low pressure switch circuit 1
10. Low pressure switch circuit 2
11. Compressor 1 high pressure
12. Compressor 2 high pressure
13. Compressor 3 high pressure
14. Compressor 4 high pressure
15. Compressor 5 high pressure
16. Compressor 6 high pressure
17. Compressor 1 overload
18. Compressor 2 overload
19. Compressor 3 overload
20. Compressor 4 overload
21. Compressor 5 overload
22. Compressor 6 overload
23. Condenser fan overload of circuit 1
24. Condenser fan overload of circuit 2
25. Condenser fan overload of circuit 1 and 2 (comun)