1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pg.100/106
46 ELECTRICAL CONNECTIONS
The instrument is provided with:
• 3 removable terminal blocks MOLEX with 0.5 mm
2
wires: 16 / 8 /22 ways for digital / analogue inputs and modulating outputs.
• 4 removable screw terminal block STELVIO for 2.5 mm
2
wires connection: 3 / 4 / 5 / 6 ways for the relay outputs.
• 5 ways connector for TTL RS485 interface outputs.
• 2 ways connector for remote panels to be connected with the cable CAB/CJ30. The remote panels have two terminals for 2.5
mm
2
wires.
• The LW30 KIT is the complete kit with MOLEX + 3 mt wires already connected and the STELVIO terminals.
• Check the connecitons and the line voltage before turning on the power supply.
• Keep low voltage cables, such as analogue/digital inputs/outputs and probes, away from power cables and terminals.
• Respect the maximum load current of each relay output, in case of power loads use filtered contactors.
47 ACCESSORIES
47.1 MONOPHASE FAN CONTROL: 230VAC AND CUT PHASE CONTROL
Models XV05PK XV10PK XV22PK
Power 500W 1000W 2200W
Ampere 2A 4A 9.5A
Scheme 1 1 1
(Scheme 1)
urenrjrjkvnm