Reference Manual
00809-0600-4026, Rev BA
December 2011
Rosemount Process Radar
7-6
Step 4. Transmitter
Diagnostics Review
Verify that no Errors or unattended Warnings are present.
For more information, see the Rosemount 5400 Series Reference Manual
(Document No. 00809-0100-4026) section “Diagnostic Messages”.
• To view Diagnostics in Rosemount Radar Master:
Rosemount Radar Master > Tools > Diagnostics
Figure 7-5. The Diagnostics
window in Rosemount Radar
Master
For more information, see the Rosemount 5400 Series Reference Manual
(Document No. 00809-0100-4026) section “Diagnostics”.
Step 5. Monitor Level
while Emptying
During Step 1, the current level reading was verified correct. This step will
verify that the transmitter correctly tracks the surface during the emptying of
the tank.
Begin by activating log functionality for the transmitter level output. Either the
DCS-trend or a stand-alone tool can be used:
Rosemount Radar Master > Tools > Log