Figure 7-3. Loop test for Analog
Out 1 - [LT-01]
Step 3. Echo-Curve
Verification at Operating
Conditions
At normal operating conditions, download and review the echo-curve
according to the following steps:
1. Check Reference Pulse amplitude and position
Compare the result against the previous plots, taken during cold start-up.
2. Review peak amplitudes and threshold settings
Verify that the surface peak is visible and that the thresholds have been
set as described in threshold settings. For information on threshold
settings, see “Threshold settings“ on page 7-3.
3. Store the echo-curve
Permanently store the echo-curve for future use, with re-occurring
verification procedures.
The reference pulse can be displayed by adjusting the plot view to show
negative values, that is up to -3.3 ft (-1 m) in the plot.
Figure 7-4. Peak amplitudes and
threshold settings
UNZ
Surface
peak
Interface
peak
Interface
threshold
Surface
threshold
Reference
peak
Distance
Amplitude