Rosemount Process Radar
3-6
Figure 3-5. Disturbing echoes
can be filtered out by creating an
amplitude threshold
1. For best performance execute Measure and Learn with an empty
tank/chamber.
2. Click Measure and Learn, and follow the instructions.
For more information, see the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530) section “The Configuration Mode Tab”.
Probe End Projection
Probe End Projection (PEP) allows you to measure product level when the
surface pulse is too weak to be detected, e.g. long measuring range, solids,
and boiling hydrocarbonates.
1. Make sure there are no disturbing echoes above the surface threshold.
2. In Rosemount Radar Master, click the Guided Probe End Projection and
follow instructions.
For more information, see the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530) section ”Probe End Projection”.
NOTE
This function is only available for liquid/solid product level measurement
modes and a well defined probe end echo (i.e. ensure that the probe
end/centering disc/weight is either always in contact with the tank wall or
never in contact with the tank wall).
NOTE
Probe End Projection is not compatible with Signal Quality Metrics, Dynamic
Vapor Compensation, high DC applications and Interface Measurement.
Amplitude Threshold Curve
Measurement signal
Amplitude, mV
Distance, m
Disturbing object