Reference Manual
00809-0600-4026, Rev BA
December 2011
6-9
Rosemount Process Radar
2. Take a back-up of the plot including the reference/antenna echo
3. Review peak amplitudes
Verify that no disturbing echoes are present above the Surface
Threshold (ATC).
Common Problems and Recommended Actions
Surface Threshold (ATC) is too low
If there are disturbing objects in the tank (e.g. nozzles, internal
obstructions, gaps between still-pipe modules) the threshold must be
set carefully to avoid locking on the wrong amplitude peak.
Figure 6-11. Surface threshold is
too low
Read Diagnostics
Verify that no Errors or unattended Warnings are present.
For more information, see the Rosemount 5400 Series Reference Manual
(Document No. 00809-0100-4026) section “Diagnostic Messages”.
To view Diagnostics in Rosemount Radar Master:
Rosemount Radar Master > Tools > Diagnostics
Figure 6-12. The Diagnostics
window in Rosemount Radar
Master
Amplitude, mV
Actual surface
Surface Threshold=
Amplitude Threshold
Curve (ATC)
Distance, m
P1 - Disturbing echo
misinterpreted as
product surface
Reference