Reference Manual
00809-0600-4026, Rev BA
December 2011
Rosemount Process Radar
5-14
8. If volume calculation is desired, choose a pre-defined Volume
Calculation Method based on a tank shape corresponding to the actual
tank. If volume calculation is not desired, choose None.
Fast Key Sequence [1,3,4,7,1]
F
OUNDATION fieldbus parameter: TRANSDUCER 1300>
VOL_VOLUME_CALC_METHOD
Choose Strapping Table if the actual tank does not match any of the
available pre-defined tank options or if high volume accuracy is desired.
Enter tank dimensions:
Diameter
Fast Key Sequence [1,3,4,7,2]
F
OUNDATION fieldbus parameter: TRANSDUCER 1300> VOL_IDEAL_DIAMETER
Length
Fast Key Sequence [1,3,4,7,3]
F
OUNDATION fieldbus parameter: TRANSDUCER 1300> VOL_IDEAL_LENGTH
Volume Offset
Fast Key Sequence [1,3,4,7,4]
F
OUNDATION fieldbus parameter: TRANSDUCER 1300> VOL_VOLUME_OFFSET
Click Next and the following window appears.
NOTE
The 4-20 mA range is not
recommended to include the
transition zone or the upper null
zone. See the Reference Manual
(Document No. 00809-0100-4026)
for details.