Reference Manual
00809-0100-4801, Rev FA
October 2010
3-17
Rosemount 3051S Series
Field Communicator v3.3
Enter the fast key sequence “Damping.”
AMS v7.0
Right click on the device and select “Configure” from the menu.
1. In the “Basic Setup” tab, enter the damping value in the “Damp” field,
click Apply.
2. After carefully reading the warning provided, select yes.
LCD DISPLAY The LCD display connects directly to the interface/electronics board which
maintains direct access to the signal terminals. The display indicates output
and abbreviated diagnostic messages. A display cover is provided to
accommodate the display.
The LCD display features a four-line display and a 0-100% scaled bar graph.
The first line of five characters displays the output description, the second line
of seven digits displays the actual value, the third line of six characters
displays engineering units and the fourth line displays “Error” when the
transmitter is in alarm. The LCD display can also display diagnostic
messages.
LCD Display Configuration with Field Communicator v3.3
The factory default LCD display setting is engineering units. The Meter
Options command allows customization of the LCD display to suit application
requirements. The LCD display will alternate between the selected items (up
to four may be chosen):
• Pressure (Engineering Units)
• Percent of Range
• Scaled Variable
• Temperature
AMS v7.0
Right click on the device and select “Configure” from the menu.
1. In the “LCD” tab, select the desired options to suit your application
needs, click Apply.
2. After carefully reading the warning provided, select yes.
Traditional Fast Keys
1, 3, 7
Device Dashboard Fast Keys
2, 2, 3