Reference Manual
00809-0100-4801, Rev FA
October 2010
7-29
Rosemount 3051S Series
Reset All Temperature Events
Selecting this will reset all values on this screen to zero with the exception of
Total Operating Time, the Total Time above and below sensor limit, and the
Number of Events for above and below sensor limit.
PROCESS ALERTS
Overview Process alerts can be used in addition to alarm or alerts generated in the
control system to indicate problems with the process or installation.
Pressure Alerts
Figure 7-23. Process Pressure
Alerts screen
Figure 7-23 shows the configuration section for Pressure Alert. If applied
pressure goes above or below the alert values, the LCD will indicate a
pressure alert and a HART alert will be generated by the transmitter. An active
alert will not affect the transmitter’s 4 – 20 mA output signal.
Alert Mode
This setting dictates whether the diagnostic is On or Off. Selecting “On
Unlatched” will generate a HART alert when the alert values are tripped.
When pressure returns to normal and within the alert limits, the alert is
automatically cleared. Selecting “On Latched” will generate the same HART
alert but will require a manual reset to clear the alert.
Latched alert action is recommended if 3rd party alert monitor software is
likely to miss alerts due to slow polling of HART data.
High Alert Value / Low Alert Value
These are independent trip values for the diagnostic. These values are
represented on the graph by the red lines.
Device Dashboard
Fast Keys
2, 3, 4, 1