Reference Manual
00809-0100-4801, Rev FA
October 2010
7-23
Rosemount 3051S Series
Resistance
This value is the calculated resistance of the electrical loop (in Ohms)
measured during the Characterize Loop procedure. Changes in the
resistance may occur due to changes in the physical condition of the loop
installation. Baseline and Previous Baselines can be compared to see how
much resistance has changed over time.
Power Supply
This value is the calculated power supply voltage of the electrical loop (in
Volts) measured during the Characterize Loop procedure. Changes in this
value may occur due to degraded performance of the power supply. Baseline
and Previous Baselines can be compared to see how much the power supply
has changed over time.
Characterization Time Stamp
This is the time stamp or elapsed time of the loop characterization event. All
time values are non-volatile and displayed in the following format:
YY:DDD:hh:mm:ss (years:days:hours:minutes:seconds).
Characterize Loop
Loop characterization must be initiated when the transmitter is first installed or
when electrical loop characteristics have been intentionally altered. Examples
include more transmitters being added onto the loop, modified power supply
level or loop resistance of the system, changing the terminal block on the
transmitter, or adding the Smart Wireless THUM to the transmitter. Another
case of required re-characterization is if the diagnostic electronics is taken out
of an existing 3051S transmitter and placed in a new 3051S installed on a
different loop.
NOTE
Power Advisory diagnostic is not recommended for transmitters operating in
HART Burst Mode (fixed current mode) or multidrop.
Severe changes in the electrical loop may inhibit HART communication or the ability to
reach alarm values. Therefore, Rosemount cannot absolutely warrant or guarantee that
the correct Failure Alarm level (HIGH or LOW) can be read by the host system at the
time of annunciation.