System Application Guide SAG584622100, SAG584622200
Spec. Nos. 584622100, 584622200, SAG584622300, SAG584622400
584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
Page 19 of 34
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
Recommended External Alarm, Reference, Monitoring, and Control Wire Sizes
Features
The system interface circuit card is mounted on the inside of the main shelf’s front door. This circuit card
provides four (4) sets of Form C relay contacts for external alarms, reference and monitoring inputs, plus
an ESTOP input. Terminal blocks are provided on the circuit card for customer connections. Refer to
Paragraphs 1.5.3 and 1.5.4 under “Specifications for details.
Restrictions
Terminal block wire size capacity is 12 to 22 AWG.
Relay contacts are rated for 1A at 30VDC or 0.3A at 110VDC.
Relays are energized for normal operating conditions and de-energized for an alarm condition.
Ordering Notes
1) Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.