System Application Guide SAG584622100, SAG584622200
Spec. Nos. 584622100, 584622200, SAG584622300, SAG584622400
584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
Page 17 of 34
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Recommended Load Distribution Wire Sizes and Lugs Selection
Features
1/4-20 x 0.625” studs on 5/8” centers are provided for installation of customer provided load distribution
leads terminated in 2-hole lugs.
Restrictions
Maximum lug width, 0.625 inches.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Load distribution lugs must be ordered separately. Customer must provide (or order) lug mounting
hardware. The rating of the distribution device determines the load lead wire size requirement. For
recommended wire sizes and lug selection for various loop lengths per fuse/circuit breaker ampere rating,
refer to Table 11. For additional lug information, refer to drawings 031110100 through 031110300.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
For wiring up to 350 kcmil, see Special Application Crimp Lugsunder ORDERING INFORMATION.
Distribution devices requiring a single distribution position require a two hole lug with 1/4” bolt
clearance holes on 5/8” centers (order per Table 11, order hardware kits per Table 7).
Distribution devices requiring two (2) or three (3) distribution positions require special application lugs
(order per Table 11 and Table 6) or busbar adapter kits (order per Table 7) and two hole lugs with
3/8” bolt clearance holes on 1” centers (order per Table 8).
Notes to Table 11:
1
Wire sizes are based on recommendations of the American National Standards Institute (ANSI)
approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16
for wire rated at 90 C conductor temperature operating in ambient temperatures of 40 C, 50°C, and
65°C was used. For other operating ambient temperatures, refer to the NEC. For operation in
countries where the NEC is not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current
for the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 50°C Ambient Operating Temperature.
5
Wire Size / Loop Length Combination Calculated using 65°C Ambient Operating Temperature.
6
These lugs are two-hole for 1/4" bolt clearance on 5/8" centers. Refer to drawing 031110100 for lug
crimping information.
7
Special application crimp lug / strap combination.
Table 11 (cont'd on next page)
Recommended Load Distribution Wire Sizes and Lugs