SAG584622100, SAG584622200 System Application Guide
SAG584622300, SAG584622400 Spec. Nos. 584622100, 584622200
Issue AC, July 3, 2012 584622300, 584622400 (Model DCS48375)
Page 12 of 34
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Bullet Nose Bypass Busbar (P/N 535015)
Features
Replaces bullet nose circuit breaker or fuseholder where protective or
disconnect device is not required.
Ordering Notes
1) Order by P/N 535015 as required.
Replacement Alarm, Reference, and Control Fuses
Ordering Notes
1) Order replacement fuses as required per Table 5.
Assembly
Desig.
Function
Size
(Amperes)
Type
Part No.
TPS/TLS
Fuseholders
(P/N 117201)
FA
Fuse Alarm
18/100
Bussmann GMT-A
248610301
--
--
--
Safety Fuse Cover
(GMT-X)
248898700
Table 5
Replaceable Alarm, Reference, and Control Fuses
Special Application Crimp Lugs, Busbar Adapter Kits, and Hardware Kits
Special Application Crimp Lugs
Features
Lug connects one (1) cable to two (2) distribution positions. Lug has 1/4” bolt clearance holes on 5/8”
centers.
Ordering Notes
1) See Table 6 for part numbers for various cable sizes.
Lead Size
Part Number
1/0 AWG
245393500
2/0 AWG
245393600
3/0 AWG
245393700
4/0 AWG
245393800
250 kcmil
514872
350 kcmil
514873
Table 6
Special Application Crimp Lugs / Strap Combination
(Two-Hole Lug, 1/4” Bolt Clearance Hole, 5/8” Centers)