System Application Guide SAG584622100, SAG584622200
Spec. Nos. 584622100, 584622200, SAG584622300, SAG584622400
584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
Page 11 of 34
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Optional Bullet Nose 6-Position GMT Distribution Fuse Block (P/N 545333)
Features
Provides six (6) load distribution fuse positions
(1/4A to 15A GMT alarm fuses).
Mounts in two (2) distribution positions.
Screw clamp type load and load return terminals provided.
Includes six (6) dummy fuses equipped with safety fuse covers.
Restrictions
When used for power distribution, load should not exceed 80% of device rating,
except 10 and 15 amp fuses, for which load should not exceed 70% of device
rating.
Occupies two (2) bullet device mounting positions.
Terminal block wire size capacity: 24 to 14 AWG.
At 40°C ambient, GMT fuses greater than 10A MUST HAVE an empty mounting
position between it and any other fuse. Maximum total current is 35A. Maximum GMT fuse size is 15A.
At 65°C ambient, GMT fuses greater than 5A MUST HAVE an empty mounting position between it and any
other fuse. Maximum total current is 21A. Maximum GMT fuse size is 10A.
Ordering Notes
1) Order optional Bullet Nose 6-Position GMT Fuse Block (P/N 545333) as required.
2) Order fuses as required per Table 4.
Replacement
Safety Fuse
Cover (GMT-Y)
Table 4
GMT Fuses