System Application Guide SAG584622100, SAG584622200
Spec. Nos. 584622100, 584622200, SAG584622300, SAG584622400
584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
Page 15 of 34
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
Wiring Notes
Refer also to the next section, Wiring Illustrations.
Recommended Frame Ground Wire Size and Lug Selection
Features
1/4-20 x 0.5” studs on 5/8” center are provided for installation of a customer provided frame ground lead
terminated in a 2-hole lug.
Ordering Notes
1) Frame ground lug must be ordered separately (hardware is provided). For recommended wire size and
lug selection, refer to Table 9. For additional lug information, refer to drawings 031110100 through
031110300.
Recm 90 C
Wire Size
1
(AWG)
Recommended
Crimp Lug
2
Vendor
Part No.
6
T & B
54205
Burndy
YAV6CL-2TC14FX
Emerson
245346700
1
Equipment grounding conductor size based on the American National
Standards Institute (ANSI) approved National Fire Protection Association's
(NFPA) National Electrical Code (NEC). Table 250-122 for copper wire
was used. If aluminum or copper clad aluminum grounding conductor is
used, refer to Table 250-122 for increased conductor size. For operation
in countries where the NEC is not recognized, follow applicable codes.
2
Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing
031110100 for lug crimping information.
Table 9
Recommended Frame Ground Wire Size and Lug
Recommended DC Inputs Wire Sizes and Lugs Selection
Features
3/8-16 x 0.875” studs on 1” centers are provided for installation of customer provided DC input leads
terminated in 2-hole lugs. Terminations are provided for each converter module (individual feed).
Adapter busbars are provided loose with each shelf which allows two (2) converter modules to be fed by
a single input.
Restrictions
Maximum lug width is 0.812 inches (individual feed) or 1.156 (dual feed).
Ordering Notes
1) DC input lugs must be ordered separately (hardware is provided). For recommended wire sizes and lug
selection, refer to Table 10. For additional lug information, refer to drawings 031110100 through
031110300.