Supported Modbus Points
5
Table 7 Liebert Nfinity - Input and Holding Registers
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale Notes/Units
Number of Input Lines 30004 40004 1 1 Bits 12 - 15
Number of Bypass Lines 30004 40004 1 1 Bits 4 - 7
Number of Output Lines 30004 40004 1 1 Bits 8 - 11
Number of Power Mod. 30010 40010 1 1 -
Number of Battery Modules Installed 30011 40011 1 1 -
Device Maximum Frame Capacity 30023 40023 2 1 -
Device System Capacity 30025 40025 2 1 VA
Nominal Input Voltage 30027 40027 1 1 V
Nominal Output Voltage 30028 40028 1 1 V
Nominal Static Bypass Switch Voltage 30029 40029 1 1 V
Nominal Input Frequency 30031 40031 1 10 Hz
Nominal Output Frequency 30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100 -
Nominal Battery Voltage 30034 40034 1 1 V
Auto Restart Delay 30051 40051 1 1 seconds
Device Auto Restart Percent Setpt 30052 40052 1 1 %
Device Low Battery Time 30053 40053 1 1 min
Next Battery Auto Test Time 30057 40057 1 1 minutes
Overload Alarm Limit 30067 40067 2 1 VA
Minimum Redundant Power Modules 30074 40074 1 1 -
Load (Apparent Power) 30102 - 2 1 VA
Load (Real Power) 30104 - 2 1 W
Load / Capacity 30106 - 1 1 %
Input Frequency 30107 - 1 10 Hz
Output Frequency 30108 - 1 10 Hz
Bypass Frequency 30109 - 1 10 Hz
Battery Charge Status 30112 - 1 -
1 - 100% Charged
2 - Less than 100%
Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage 30113 - 1 1 V
Battery Time Remaining 30115 - 1 1 min
Battery Charge Percentage 30116 - 1 1 %
Battery Temperature 30117 - 1 1 degrees C
Transformer Temperature 30121 - 1 1 degrees C
Redundant Power Modules 30124 - 1 1 -
Active Power Module Count 30126 - 1 1 -