Supported Modbus Points
6
Table 7 Liebert Nfinity - Input and Holding Registers
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale Notes/Units
Battery Module Active Count 30127 - 1 1 -
Battery Test Result 30130 - 1 1 -
Input Voltage L1 30153 - 1 1 V
Input Current L1 30154 - 1 1 A
Bypass Voltage L1 30159 - 1 1 V
Bypass Current L1 30160 - 1 1 A
Output Voltage L1 30163 - 1 1 V
Output Current L1 30164 - 1 1 A
Power Module Failure Count 30304 - 1 1 -
Battery Module Failure Count 30305 - 1 1 -
Power Module Warning Count 30306 - 1 1 -
Battery Module Warning Count 30307 - 1 1 -