Supported Modbus Points
4
2.0 SUPPORTED MODBUS POINTS
This section includes two types of tables—(a) Status and Coil and (b) Input and Holding
Registers—for each Liebert unit.
Note for Input and Holding Registers tables: a value read from an input register is the real-time
data value; a value read from a holding register is the value last set to this Modbus server by a user.
Table 6 Liebert Nfinity
®
- Status and Coil
Data Point Status Coil Number of Bits Notes/Units
Automatic Battery Test Enabled 10003 3 1 -
Battery Charger On 10044 - 1 -
Inverter Ready 10047 - 1 -
Power Factor Correction State 10050 - 1 -
Load on Inverter 10073 - 1 -
Bypass Active 10074 - 1 -
Replace Battery 10081 - 1 -
Battery Under Test 10082 - 1 -
Load on Battery 10128 - 1 -
Load on Bypass 10129 - 1 -
Load on Manual Bypass 10132 - 1 -
Load Transferred to Bypass
Due to UPS Fault
10134 - 1 -
Transfer Inhibit 10146 - 1 -
Output Off Pending 10151 - 1 -
Low Battery - Shutdown Imminent 10152 - 1 -
Output Overload 10154 - 1 -
UPS Overload 10155 - 1 -
Output Off 10158 - 1 -
Check Air Filter - Replace 10170 - 1 -
Transformer Over Temperature 10178 - 1 -
Input Power Supply Fail 10186 - 1 -
Internal Device Communication Failure 10284 - 1 -
Device Active Alarm 10290 - 1 -
Main Control Warning 10291 - 1 -
Redundant Control Warning 10292 - 1 -
Control Module Failure 10293 - 1 -
Redundant Control Module Failed 10294 - 1 -
User Interface Module Failed 10295 - 1 -
UPS Power Not Redundant 10296 - 1 -
Power Module Failure 10298 - 1 -
Battery Module Failure 10299 - 1 -
Power Module Warning 10300 - 1 -
Battery Module Warning 10301 - 1 -