Supported Modbus Points
42
Table 27 Liebert XDF - Input and Holding Registers
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Note
Vendor ID 30001 40001 1 1
-
Device ID 30002 40002 1 1
-
Version number 30003 40003 1 1
-
UPS/Env/Pwr 30004 40004 1 1
-
Timer Mode
1
30016 40016 1 1
-
Type of DT Room-FC
2
30017 40017 1 1
-
Temperature Setpoint 30023 40023 1 x10 C°
Delay after safe Temp has been
reached
30034 40034
- -
Minute
Allowable deviation between internal
temp sensors
30035 40035
- -
C°
High Temperature 30050 40050 1 x10 C°
Low Temperature 30051 40051 1 x10 C°
High Cabinet Temperature Setpoint 30058 40058
-
x10 C°
Low Cabinet Temperature Setpoint 30059 40059
-
x10 C°
Fan Run Hour Threshold 30070 40070
-
1 Hour
Compressor 1 Run Hour Threshold 30071 40071
-
1 Hour
Service Ramp 30099
- -
1 %
Operating State
6
30100
- -
1
-
Number of Active Events/Alarm 30101
- - - -
Summary Alarm Status
7
30102
- - - -
Fan Ramp 30103
- -
1 %
Cooling Ramp 30104
- -
1 %
Actual Temperature SP 30111
- -
x10 C°
Digital Scroll Compressor 1
High Temperature
30119
- -
x10 C°
Sensor 1 Temp 30121
- - -
C°
Sensor 2 Temp 30122
- - -
C°
Sensor 3 Temp 30123
- - -
C°
Sensor 4 Temp 30124
- - -
C°
Ambient Temp 30125
- - -
C°
Ambient Humidity 30126
- - -
%
Dew Point Temp 30127
- - -
C°
Adjusted Setpoint Temp 30128
- - -
C°
Cabinet Temperature 30129
- - -
C°
Service Due Year Month 30135
- - - -
Device kW Load 30136
- - -
kW
Fan Run Hour 30141
- -
1 Hour
Compressor 1 Run Hour 30142
- -
1 Hour
Daily High Temperature 30151
- -
x10 C°