Supported Modbus Points
22
Table 15 Liebert GXT2 - Input and Holding Registers
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale Notes / Units
Battery Test Result 30130 - 1 -
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1 30153 - 1 1 V
Bypass Voltage L1 30159 - 1 1 V
Output Voltage L1 30163 - 1 1 V
Output Current L1 30164 - 1 1 A
Input Maximum Voltage L1 30180 - 1 1 V
Input Minimum Voltage L1 30181 - 1 1 V
Output Maximum Voltage L1 30182 - 1 1 V
Output Minimum Voltage L1 30183 - 1 1 V
Black Out Count 30301 - 1 1 -
Brown Out Count 30302 - 1 1 -