Supported Modbus Points
39
Table 26 Liebert XDF
™
- Status and Coil
Data Description Status Coil Number of Bits Notes
Temperature Indication
1
10011 11 1
-
Unit Control
- 25 1
-
Reset Alarm
- 26 1
-
Acknowledge Alarm
- 27 1
-
Cabinet Sensor Alarm Enable
10023 23 1
-
Safe Door Open Symbol
10024 24 1
-
Fan On
10025 - 1
-
Cool On
10026 - 1
-
Digital Scroll Compressor 1 High
Temperature
10045 - 1
-
Smoke Detected
10047 - 1
-
Water Under Floor
10048 - 1
-
Humidifier Problem
10049 - 1
-
Stby Glycol Pump On
10050 - 1
-
Standby Unit On
10051 - 1
-
Cond Pump-High Water
10052 - 1
-
Room Sensor Failure
10053 - 1
-
Loss Compressor Power
10054 - 1
-
Loss of Air Blower 1
10055 - 1
-
Humidifier Low Water
10058 - 1
-
Humidifier High Amps
10059 - 1
-
High Temperature
10060 - 1
-
Loss of Power
10061 - 1
-
Remote Shutdown
10062 - 1
-
Unspecified Event(s)
1
10064 - 1
-
High CW Temp
10065 - 1
-
Reserved
10066 - 1
-
High Room Temp
10067 - 1
-
Low Room Temp
10068 - 1
-
High Room Hum
10069 - 1
-
Low Room Hum
10070 - 1
-
High Temp Sensor A
10071 - 1
-
Low Temp Sensor A
10072 - 1
-
High Hum Sensor A
10073 - 1
-
Low Hum Sensor A
10074 - 1
-
Loss of CW Flow
10075 - 1
-
Clogged Filters
10076 - 1
-
Supply Sensor Failure
10077 - 1
-
Freecool Temp Sensor
10078 - 1
-
Kommentare zu diesen Handbüchern