Table 3-4. Rosemount (standard) alarm and saturation values
Table 3-5. NAMUR-Compliant alarm and saturation values
Table 3-6. Custom alarm and saturation values
The following limitations exist for custom levels:
Low alarm level must be less than the low saturation level
High alarm level must be higher than the high saturation level
Alarm and saturation levels must be separated by at least 0.1 mA
Alarm and saturation level configuration
The Alarm/Sat Levels tab allows the Alarm and Saturation Levels to be configured. To change
alarm/saturation level settings, click on the Config Alarm/Sat Levels button.
Figure 3-18. Device - alarm/sat levels tab
Level Saturation Alarm
Low 3.9 mA 3.75 mA
High 20.8 mA 21.75 mA
Level Saturation Alarm
Low 3.8 mA 3.6 mA
High 20.5 mA 22.5 mA
Level Saturation Alarm
Low 3.7 mA — 3.9 mA 3.6 mA — 3.8 mA
High 20.1 mA — 22.9 mA 20.2 mA — 23.0 mA
Mass and Energy Flow Fast Keys 1, 4, 2, 6, 6
Direct Process Var. Output Fast Keys 1, 4, 2, 6, 6