Reference Manual
00809-0100-4803, Rev DA
Appendix A: Reference Data
April 2013
Specifications and Reference Data
Line Pressure effect
(1)
Mounting Position Effects
Vibration effect
Less than ±0.1% of URL when tested per the requirements of IEC60770-1 field or pipeline with
high vibration level (10-60 Hz 0.21mm displacement peak amplitude / 60-2000 Hz 3g).
For Housing Style codes 1J, 1K, and 1L:
Less than ±0.1% of URL when tested per the requirements of IEC60770-1 field with general
application or pipeline with low vibration level (10-60 Hz 0.15mm displacement peak amplitude
/ 60-500 Hz 2g).
Models Ultra
per 50 °F (28 °C)
Classic or Classic MV
per 50 °F (28 °C)
Ultra for Flow
(2)
-40 to 185 °F (-40 to 85 °C)
3051SMV_ _ 3: Differential Pressure & Temperature
3051SMV_ _ 4: Differential Pressure
Range 2 - 5
(3)
± (0.009% URL + 0.025% span)
from 1:1 to 10:1;
± (0.018% URL + 0.08% span)
from >10:1 to 200:1
± (0.0125% URL + 0.0625% span)
from 1:1 to 5:1;
± (0.025% URL + 0.125% span)
from >5:1 to 100:1
±0.13% reading up to 8:1 DP
turndown from URL;
±[0.13 + 0.0187
(URL/RDG
(4)
)] % reading to
100:1 DP turndown from URL
Range 0 ± (0.25% URL + 0.05% span)
from 1:1 to 30:1
± (0.25% URL + 0.05% span)
from 1:1 to 30:1
N/A
Range 1 ± (0.1% URL + 0.25% span)
from 1:1 to 50:1
± (0.1% URL + 0.25% span)
from 1:1 to 50:1
N/A
Process Temp.
RTD Interface
(5)
N/A ±0.39 °F (0,216 °C) per 50 °F (28 °C)
±0.39 °F (0,216 °C) per 50 °F
(28 °C)
(1) Ultra for Flow is only available for 3051SMV DP Ranges 2-3.
(2) Ultra for Flow is only available for 3051SMV DP Ranges 2-3.
(3) Use Classic specification for 3051SMV DP Range 5 Ultra.
(4) RDG refers to transmitter reading.
(5) Specifications for process temperature are for the transmitter portion only. The transmitter is compatible with any Pt 100 (100 ohm platinum) RTD. Examples of
compatible RTDs include Rosemount Series 68 and 78 RTD Temperature Sensors.
Models
(1)
(1) For zero error specifications for line pressures above 2000 psi (137,9 bar) or line pressure effect specifications for DP Ranges 4-5, see the 3051SMV Reference Manual
(document number 00809-0100-4803).
Ultra and Ultra for Flow Classic and Classic MV
3051SMV: Differential Pressure Measurement Only
Range 2-3
Range 0
Range 1
Range 2-3
Range 0
Range 1
Zero Error
(2)
± 0.025% URL per 1000 psi (69 bar)
± 0.125% URL per 100 psi (6,89 bar)
± 0.25% URL per 1000 psi (69 bar)
Span Error
(3)
± 0.1% of reading per 1000 psi (69 bar)
± 0.15% of reading per 100 psi (6,89 bar)
± 0.4% of reading per 1000 psi (69 bar)
(2) Zero error can be zeroed.
(3) Specifications for option code P0 are 2 times those shown above.
Zero Error
(2)
± 0.05% URL per 1000 psi (69 bar)
± 0.125% URL per 100 psi (6,89 bar)
± 0.25% URL per 1000 psi (69 bar)
Span Error
(3)
± 0.1% of reading per 1000 psi (69 bar)
± 0.15% of reading per 100 psi (6,89 bar)
± 0.4% of reading per 1000 psi (69 bar)
Models Ultra, Ultra for Flow, Classic and Classic MV
3051SMV_ _ 1, 2 DP:
AP/GP:
Zero shifts up to ±1.25 inH
2
O (3,11 mbar), which can be zeroed; no span effect
Zero shifts to ±2.5 inH
2
O (6,22 mbar), which can be zeroed; no span effect
3051SMV_ _ 3, 4 Zero shifts up to ±1.25 inH
2
O (3,11 mbar), which can be zeroed; no span effect
Seitenansicht 134