Table 43 Liebert Series 300 UPS - Input and Holding Registers
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines 30004
40004
1
-
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
-
Bits 4 - 7
Number of Output Lines
30004
40004
1
-
Bits 8 - 11
Number of SubModules
30009
40009
1
-
-
Load Circuit Present 30013
40013
1 -
There are 16 possible Load
Circuits. Each bit represents 1
Load Circuit. Load Circuit 1 is
bit 0, Load Circuit 2 is bit 1
and so on. If the bit is 1, then
the Load Circuit is supported.
Nominal Power Rating
30021
40021
2
-
VA
Nominal Input Voltage
30027
40027
1
-
V
Nominal Output Voltage
30028
40028
1
-
V
Nominal Static Bypass Switch
Voltage
30029
40029
1
-
V
Nominal Input Current
30030
40030
1
-
A
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
-
Nominal Battery Voltage
30034
40034
1
-
V
Device Low Battery Time
30053
40053
1
-
Minutes
Load (Apparent Power)
30102
-
2
-
VA
Load (Real Power)
30104
-
2
-
W
Load / Capacity
30106
-
1
-
%
Input Frequency
30107
-
1
10
Hz
Output Frequency
30108
-
1
10
Hz
Bypass Frequency
30109
-
1
10
Hz
Battery Charge Status 30112 - 1
-
1 - 100% Charged
2 - Less than 100% Charged
Battery Voltage
30113
-
1
-
V
Battery Current
30114
-
1
-
A
Battery Time Remaining
30115
-
1
-
Minutes
Battery Charge Percentage
30116
-
1
-
%
Battery Test Result 30130 - 1
-
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1
30153
-
1
-
V
Input Current
30154
-
1
-
A
Bypass Voltage L1
30159
-
1
-
V
Bypass Current L1
30160
-
1
-
A