3B
UPS Systems
63
Table 29 Liebert NXL with Liebert iCOM Single Module (SMS) - Input and Holding Registers
Bypass Input Wire Configuration
30352
-
1
-
(single phase + return)
1=Two Wire
(2 phase, no neutral)
2=Three Wire
(2 phase + neutral)
3=Three Wire
(3 phase, no neutral)
4=Four Wire
Output Wire Configuration
30353
-
1
-
(single phase + return)
1=Two Wire
(2 phase, no neutral)
2=Three Wire
(2 phase + neutral)
3=Three Wire
(3 phase, no neutral)
4=Four Wire
Battery Cell Count - Lead Acid
Battery Cell Count-Nickel
Cadmium
30355
-
1
- -
UPS System Output Source
30356
-
1
-
1=Normal
2=Bypass
Battery Volts for Cabinet
Array Index 1
30358
-
1
-
VDC
Battery Volts for Cabinet
Array Index 2
30359
-
1
-
VDC
Battery Volts for Cabinet
30360
-
1
-
VDC
Battery Volts for Cabinet
Array Index 4
30361
-
1
-
VDC
Battery Volts for Cabinet
Array Index 5
30362
-
1
-
VDC
Battery Volts for Cabinet
30363
-
1
-
VDC
Battery Volts for Cabinet
Array Index 7
30364
-
1
-
VDC
Battery Volts for Cabinet
Array Index 8
30365
-
1
-
VDC
Battery Temperature for Cabinet
Array Index 1
30366
-
1
-
deg C
Battery Temperature for Cabinet
30367
-
1
-
deg C
Battery Temperature for Cabinet
Array Index 3
30368
-
1
-
deg C