3B
UPS Systems
58
Table 28 Liebert NXL
with Liebert iCOM Single Module (SMS) - Status and Coil
Data Description
Status
Coil
Number of Bits
Notes
Battery Circuit Breaker 3 Open
10342
-
1
Active on Alarm
Battery Circuit Breaker 4 Open
10343
-
1
Active on Alarm
Battery Circuit Breaker 5 Open
10344
-
1
Active on Alarm
Battery Circuit Breaker 6 Open
10345
-
1
Active on Alarm
Battery Circuit Breaker 7 Open
10346
-
1
Active on Alarm
Battery Circuit Breaker 8 Open
10347
-
1
Active on Alarm
Battery - External Monitor 1
10348
-
1
Active on Alarm
Battery - External Monitor 2
10349
-
1
Active on Alarm
Battery Over Temperature
10350
-
1
Active on Warning
DC Bus Ground Fault - Positive
10351
-
1
Active on Alarm
DC Bus Ground Fault - Negative
10352
-
1
Active on Alarm
System Output Low Power Factor
10353
-
1
Active on Alarm
Leading Power Factor
10354
-
1
Active on Alarm
Output Amp Over User Limit -
Phs A
10355 - 1 Active on Alarm
Output Amp Over User Limit -
Phs B
10356 - 1 Active on Alarm
Output Amp Over User Limit -
Phs C
10357 - 1 Active on Alarm
System Output Fault
10358
-
1
Active on Alarm
Inverter Overload Phase A
10359
-
1
Active on Alarm
Inverter Overload Phase B
10360
-
1
Active on Alarm
Inverter Overload Phase C
10361
-
1
Active on Alarm
Inverter Inhibit - External
10362
-
1
Active on Alarm
Inverter Shutdown - Overload
10363
-
1
Active on Alarm
Inverter Off - External
10364
-
1
Active on Alarm
Inverter Static Switch SCR Short
10365
-
1
Active on Alarm
Equipment Over Temperature
10366
-
1
Active on Warning
Equipment Over Temperature
10367
-
1
Active on Alarm
Equipment Temperature Sensor
Fail
10368 - 1 Active on Alarm
Input Contact 01
10369
-
1
Active on Alarm
Input Contact 02
10370
-
1
Active on Alarm
Input Contact 03
10371
-
1
Active on Alarm
Input Contact 04
10372
-
1
Active on Alarm
Input Contact 05
10373
-
1
Active on Alarm
Input Contact 06
10374 - 1 Active on Alarm
Input Contact 07
10375
-
1
Active on Alarm
Input Contact 08
10376
-
1
Active on Alarm
Input Contact 09
10377
-
1
Active on Alarm
Input Contact 10
10378
-
1
Active on Alarm