Emerson Liebert FPC Bedienungsanleitung Seite 10

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 100
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 9
1B
Precision Cooling Products
6
Table 6 Liebert CRV
- Status and Coil
Data Description
Status
Coil
Number of Bits
Notes
Compressor 1 Low Suction
Pressure
10032 - 1 Active on Alarm
Compressor 1 Hours Exceeded
10033
-
1
Active on Alarm
Dig Scroll Comp 1 Temp Sensor
Issue
10034 - 1 Active on Alarm
Dig Scroll Comp 1 Over Temp
10035
-
1
Active on Alarm
Compressor 1 Low Pressure
Transducer Issue
10036 - 1 Active on Alarm
Ext Compressor Lockout
10037
-
1
Active on Alarm
Compressor 1 Short Cycle
10038
-
1
Active on Alarm
Compressor 1 High Pressure
Transducer Issue
10039 - 1 Active on Alarm
Compressor 1 Pump Down Issue
10040
-
1
Active on Alarm
Reheater Over Temperature
10041
-
1
Active on Alarm
Electric Reheater 1 Hours
Exceeded
10042 - 1 Active on Alarm
Ext Reheat Lockout
10043
-
1
Active on Alarm
Condenser 1 Issue
10044
-
1
Active on Alarm
Condenser VFD Issue
10045
-
1
Active on Alarm
Condenser TVSS Issue
10046
-
1
Active on Alarm
Supply Chilled Water Over Temp
10047
-
1
Active on Alarm
Chilled Water Control Valve
Position
10048 - 1 Active on Alarm
Supply Chilled Water Loss of Flow
10049
-
1
Active on Alarm
Supply Fluid Temp Sensor Issue
10050
-
1
Active on Alarm
Customer Input 1
10051
-
1
Active on Alarm
Customer Input 2
10052
-
1
Active on Alarm
Customer Input 3
10053
-
1
Active on Alarm
Customer Input 4
10054
-
1
Active on Alarm
Smoke Detected
10055
-
1
Active on Alarm
Water Under Floor
10056
-
1
Active on Alarm
Service Required
10057
-
1
Active on Alarm
Shutdown - Loss Of Power
10058
-
1
Active on Alarm
Ext Over Temperature
10059
-
1
Active on Alarm
Ext Loss of Flow
10060
-
1
Active on Alarm
Ext Condenser Pump High Water
10061
-
1
Active on Alarm
Ext Standby Glycol Pump On
10062
-
1
Active on Alarm
External Fire Detected
10063
-
1
Active on Alarm
Unit On
10064
-
1
Active on Alarm
Unit Off
10065
-
1
Active on Alarm
Unit Standby
10066
-
1
Active on Alarm
Unit Partial Shutdown
10067
-
1
Active on Alarm
Unit Shutdown
10068
-
1
Active on Alarm
Seitenansicht 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 99 100