Table 7 Liebert CRV - Input and Holding Registers
Remote Sensor Function
Module Index 8
30471 40471 1 -
1=Reference
Remote Sensor Function
Module Index 9
30472 40472 1 -
1=Reference
Remote Sensor Function
Module Index 10
30473 40473 1 -
1=Reference
System Status
30474 - 1 -
2=Startup
8=Normal with Warning
16=Normal with Alarm
System Operating State
30475 - 1 -
1=On
System Control Mode
30476 - 1 -
0=Internal (Auto)
1=External (Manual)
System Operating State Reason
30477 - 1 -
1=Network Display
2=Alarm
3=Schedule
4=Remote System
5=External Input
System On/Off Control
30478 40478 1 -
System Event
Acknowledge/Reset
- 40479 1 -
If the Scale column has a value for a data point, multiply the Modbus value by the value in the Scale column.