Operation and Display Panel
Liebert
®
APS
54
4.3.7 Settings Screen
From the main screen, press the F4 button four times until the settings screen is displayed. The
settings screen is displayed in a total of nine screens as you scroll down, as shown in Figure 62.
Figure 62 Settings screens
On the first settings screen, pressing the F5 button will prompt a password window to pop up. After
you enter the correct password, the function of the F2, F3, and F4 buttons will switch from the
primary functions to the secondary functions, as shown in Table 23.
4.4 Entering a Password
1. On the password prompt window, press the F5 button, the first digit will become editable, press
the F3 button to enter the correct number.
2. Press the F4 button, the second digit will become editable, press the F3 button to enter the correct
number.
3. Enter the rest of the password digits using the same method in Step 2, and press the F5 button
when complete.
Set Redundancy Mode
Remote Comms Shutdown
Bypass Setting
Output Frequency
Output Voltage
Inverter Sync Range
Settings
Liebert APS
2014-01-01
10:45:20
Disabled
Enabled
Enabled
50Hz
230
± 5.0Hz
First Screen
Third Screen Fourth Screen
Remote Shutdown Delay
Bypass Upper Limit
Bypass Lower Limit
Guaranteed Shutdown
Bypass Alarm Mode
Set RS 232 Protocol
Settings
Liebert APS
2014-01-01
10:45:20
2second
+10%
-15%
Disabled
Enabled
INTERFACE2
ESC
Auto-Restart Mode
Auto-Restart Capacity
Auto-Restart Delay
Display Contrast
Date & Time
Command Password
Settings
Liebert APS
2014-01-01
10:45:20
Enabled
20%
12second
*******
2014 -01-01 10 :45:20
ESC
Max Load Alarm
Max Load Threshold
Redundant Alarm Mode
Communication Address
Air Filter Reminder
Air Filter Type
Settings
Liebert APS
2014-01-01
10:45:20
Disabled
0.0kVA
Disabled
1
Disabled
Standard
Second Screen
IT System Compatibility
UPS ID
Company Name
Contact Number
Load Factory Default
Settings
Liebert APS
2014-01-01
10:45:20
No
Disabled
Fifth Screen