Emerson Liebert APS Bedienungsanleitung Seite 43

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 108
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 42
Installation
35 Liebert
®
APS
Figure 43 Connecting external battery cabinet (transformer-based UPS)
After connecting the external battery cabinet, use the user interface to determine the number of
external battery cabinets, as shown in Figure 44.
Figure 44 Battery screen
If the number displayed is not consistent with the actual installation number of external battery
cabinets:
Ensure each external battery cabinet contains two battery modules installed on the same row and
both have the locking levers in the locked position.
Ensure the Liebert IntelliSlot EBC card is installed properly and the communication cables are
fully inserted in the connectors.
Determine that the DIP switch setting of each battery cabinet is correct using the following table
Table 13 EBC DIP switch settings
External Battery
Cabinet Number
DIP Switch Setting
12
EBC #1 UP UP
EBC #2 Down UP
EBC #3 UP Down
EBC #4 Down Down
Battery Cabinet
Liebert APS
Communication
Cable
Battery
Cable
Battery
Batt temp ( C)
Discharge count
Discharge hour (H)
Ext batt-cab count
Liebert APS
2012-01-01
10:45:20
Ʒ
25.0
303
9.4
0
Ʒ
ESC
e
Seitenansicht 42
1 2 ... 38 39 40 41 42 43 44 45 46 47 48 ... 107 108

Kommentare zu diesen Handbüchern

Keine Kommentare