  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 55
Emerson Climate TechnologiesEmerson Climate TechnologiesTemperature-Pressure Controls
52
Emerson Climate Technologies
PSC Pressure Switch
The Emerson PSC is a Pressure Switch with xed
switch-point settings.
Features
• Maximum Operating Pressure up to 623 psig Test
Pressure up to 696 psig
• Standard factory settings from stock in small volumes
• High and low pressure switches
• High temperature version with snubber for direct com-
pressor mounting (Range 6)
• Direct mounting reduces the number of joints and thus
avoiding potential leakage
• Precise setting and repeatability
• IP 65 protection if used with the cables with plug
Options
For direct mounting on a pressure connection
(free standing) or with a capillary tube
Direct compressor head mounting with high
temperature bellows and snubber
- reduces the number of joints
- avoids potential leakage
- saves high cost of exible hose
TÜV approved versions for high and low pressure
Micro-switch for narrow pressure differentials
Gold plated contacts for low voltage/current
applications
Cables with plug ordered separately
PSC Introduction
PSC is equipped with a SPDT snap action contact,
switching from 1-2 to 1-4 on rising pressure and from 4
to on falling pressure (see diagram). Several models are
available:
• Low pressure switch, with automatic or manual reset
• High pressure switch, with automatic or manual reset
• DIN/TÜV approved safety high pressure limiter with
automatic reset
• DIN/TÜV approved safety high pressure cut-out, with
internal or external manual reset
TÜV approval for pressure switches can be reached
either by using a double diaphragm (Pressure range
1-5) which acts in a fail-safe mode or by a single pres-
sure element (Bellows, Pressure range 6) which is able
to resist to >Mio. cycles between 50% and 100% of the
maximum operating pressure (see 4.6.1 of EN 12263).
PSC
1
P
2
4
+
-
Bellows (Pressure Range 6)
Single Diaphragm
Seitenansicht 55