Instruction Manual
D103621X012
4320 Position Monitor
April 2014
24
Pneumatic Hookup Procedures for On/Off Control Option
WARNING
To avoid personal injury or property damage resulting from bursting of parts, do not exceed maximum supply pressure.
Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and
appropriate preventive measures are not taken. Preventive measures may include, but are not limited to, one or more of
the following: Remote venting of the unit, re‐evaluating the hazardous area classification, ensuring adequate ventilation,
and the removal of any ignition sources. For information on remote venting of this controller, refer to page 26.
Severe personal injury or property damage may occur from an uncontrolled process if the instrument supply medium is not
clean, dry, oil‐free, and noncorrosive. While use and regular maintenance of a filter that removes particles larger than 40
micrometers in diameter will suffice in most applications, check with an Emerson Process Management field office and
industry instrument air quality standards for use with corrosive air or if you are unsure about the amount of air filtration or
filter maintenance.
WARNING
When using natural gas as the supply medium the following also applies:
D When disconnecting any of the pneumatic connections or any pressure retaining part, natural gas will seep from the
unit and any connected equipment into the surrounding atmosphere. Personal injury or property damage may result if
natural gas is used as the supply medium and appropriate preventive measures are not taken. Preventive measures
may include, but are not limited to, one or more of the following: ensuring adequate ventilation and the removal of any
ignition sources.
Supply pressure must be clean, dry, air that meets the requirements of ISA Standard 7.0.01.
Alternatively, natural gas must be clean, dry, oil-free, and noncorrosive. H
2
S content should not exceed 20 ppm.
A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer
particle size is recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis.
Condensation in the air supply should be minimized.
Use of a 67CFR filter regulator with standard 5 micrometer filter, or equivalent, to filter and regulate supply air should
suffice in most applications. The 67CFR filter regulator can be integrally mounted with the position monitor. Supply
connections are 1/4 NPT.
Prior to connecting the supply air to the spool valve, flush the system to remove any debris or contaminates.
4-Way Spool Valves
The spool valve is a 5 port, 4-way valve driven by an internally mounted pilot. Refer to figure 18 for spool valve supply
port and work ports locations and installation options.
CAUTION
Failure to install the supplied vents in the exhaust ports (ports 3 and 5) can result in damage to the seals.