Instruction Manual
D103621X012
4320 Position Monitor
April 2014
17
Figure 8. Installation Drawing Notes; See Figure 9 for Battery Module Assembly & Figure 10 for External Power Option
INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL WIRING PRACTICES OF THE COUNTRY IN USE.
BARRIERS MUST BE CONNECTED PER MANUFACTURE'S INSTALLATION INSTRUCTIONS.
INTRINSICALLY SAFE APPARATUS MAY BE CONNECTED TO ASSOCIATED APPARATUS NOT SPECIFICALLY
EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Ui) AND
THE CURRENT (Ii) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE
VOLTAGE (Uo) AND CURRENT (Io) DEFINED BY THE ASSOCATED APPARATUS. IN ADDITION, THE SUM OF
THE MAXIMUM UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF EACH INTRINSICALLY SAFE
APPARATUS, AND THE INTERCONNECTING WIRING, MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Co)
AND INDUCTANCE (Lo) DEFINED BY THE ASSOCIATED APPARATUS. IF THESE CRITERIA ARE MET, THEN THE
COMBINATION MAY BE CONNECTED.
FORMULAS Ui > Uo
Ii > Io
Ci + Ccable < Co
Li + Lcable < Lo
Pi > Po
RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM.
IF HAND-HELD COMMUNICATOR OR MULTIPLEXER IS USED, IT MUST BE APPROVED WITH ENTITY
PARAMETERS AND INSTALLED PER THE MANUFACTURER'S CONTROL DRAWING.
WARNING
THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED TO CONSTITUTE
A POTENTIAL RISK OF IGNITION BY IMPACT OR FRICTION. AVOID IMPACT AND FRICTION
DURING INSTALLATION AND USE TO PREVENT RISK OF IGNITION.
GE59530-B, sheet 1
Figure 9. Installation Drawing for Battery Module Assembly; See Notes in Figure 8
HART COMM TERMINALS
WP1/WP2
BATTERY
MODULE
ASSEMBLY
HAND HELD
HAZARDOUS LOCATION NON-HAZARDOUS LOCATION
INTRINSICALLY SAFE
CLASS I DIV 1 GP ABCD
CLASS I, ZONE 0 GP IIC
4320 POSITION MONITOR
Ui = 6.0 V
Ii = 5 mA
Pi = 30 mW
Ci = 2.5 nF
Li = 0 mH
Uo = 6.0 V
Io = 14 mA
Po = 84 mW
Co = 39 mf
Lo = 150 mH
HART COMM TERMINALS
(BATTERY MODULE - WP1 / WP2)
GE59530-B, sheet 1
MAIN BOARD
ASSEMBLY
Seitenansicht 16