Instruction Manual
D103621X012
4320 Position Monitor
April 2014
21
Sliding‐Stem (Linear) Actuators (e.g. Fisher 667)
Before mounting, verify that linear travel is greater than one‐half and not more than the maximum recommended
travel of the feedback kit.
1. Attach the mounting bracket to the actuator.
2. Loosely attach the feedback pieces and magnet assembly to the valve stem connector. Do not tighten the fasteners
because fine adjustment is required.
CAUTION
Do not install a magnet assembly that is shorter than the physical travel of the actuator. Loss of control will result from the
magnet assembly moving outside the range of the index mark in the feedback slot of the 4320 housing.
3. Center the magnet assembly inside the retaining slot 5.7 mm (0.22 inch) away from the bottom base of the
housing as measured from the center of the assembly bolt holes to the base of the housing (see figure 13).
4. Align the magnet assembly as shown in figure 13.
5. Tighten the fasteners.
6. Mount the wireless positioner monitor to the mounting bracket, using the mounting bolts. Any of the mounting
holes may be used for linear actuators. See figure 14.
7. Once the instrument is mounted perform the local interface calibration procedure, as described on page 31. Verify
the magnet assembly position through the entire travel range before putting into service.
Figure 13. Mounting—Sliding‐Stem Magnet Assembly
GE59830
MOUNTING FACES
MOUNTING
FACES
mm
(INCH)
MAGNET
ASSEMBLY
BOLT
BASE OF
HOUSING
5.7 $ 2.0
(0.22 $ 0.08)