Instruction Manual
D103621X012
4320 Position Monitor
April 2014
14
Figure 7. Wireless Setup
CONFIGURE
CONFIGURE
PUBLISHING
GUIDED SETUP
JOIN DEVICE TO NETWORK
There are three burst messages that can be configured. Each can have its own content, one of five trigger modes, and
a range of update rates. Burst messages may be set to default values or tailored to your application in Configure
Publishing. Refer to Broadcast Information on page 37 for additional information on burst configuration.
6. Remove the leads from the 4320 and close the cover. Tighten the instrument cover screws to a torque of 5.6 to
6.7 N•m (50 to 60 lbf•in).
7. Install the 4320 on monitored equipment and/or verify the 1420 gateway.
Note
1410 gateway version 4.4.28 or later or 1420 gateway version 4.4.15 or later is required.