Installation and User Instructions UM584622100
Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
Chapter 4. Making Electrical Connections Page 21
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
EXPANSION SHELF(S) INTERCONNECTIONS
Installing Output Paralleling Leads
Procedure
1) Perform the procedure in Figure 4-5 for each expansion shelf.
Cable, lugs (P/N 144511), and labels are
provided loose with the Expansion Shelf
to assemble a Return and a -48V
paralleling cable.
1. Cut the cables to the proper length.
2. Lug the cables
(use standard brown die for 2 ga. cable).
3. Connect cables between terminals
as indicated below. Torque to 58 in-lbs.
4. Re-Install Expansion Wiring Covers.
(refer to procedure in the
“Installing the System” chapter.)
Expansion
Wiring Covers
Hardware provided
on terminals.
RETURN
PARALLELING
CABLE
-48V
PARALLELING
CABLE
584622100 / 584622200 shown.
584622300 / 584622400 similar.
Figure 4-5
DC Output Paralleling Interconnections