Emerson NetSure DCS 48375 Bedienerhandbuch Seite 25

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 44
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 24
Installation and User Instructions UM584622100
Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
Chapter 4. Making Electrical Connections Page 19
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Load Distribution Connections
* 1/4-20 x 0.625studs on 5/8centers
for installation of leads with 2-hole lugs.
* Maximum lug width 0.625.
* Torque to 58 in-lbs.
-48VDC
Return
Front
Front
Components removed in
illustration for clarity only.
Load
Distribution
Leads Enter
Here (break
tabs off shield
as required)
P/N 545405
P/N 545404
P/N 545571
Top Cover Removed in
Illustration for Clarity Only
Optional Busbar Adapters
584622100 / 584622200 shown.
584622300 / 584622400 similar.
Figure 4-3
Load Connections to Distribution Bus Row
Seitenansicht 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 43 44

Kommentare zu diesen Handbüchern

Keine Kommentare