Instruction Manual
D103597X012
D4 Valve with easy-Drive Actuator
November 2013
13
D 0=L2e(Dualdrycontact)
D 1=Singledrycontact
Configuration Software
D Use radio button to select L2e or Single pole local digital control when Control Source is set to Local.
Calibration Instructions
WARNING
To avoid personal injury or property damage, be aware that the valve will open fully and then close fully during the
calibration cycle.
It is not necessary to calibrate y our easyDrive electric actuator prior to use from a factory shipment.
If any of the following are true, recalibration will be required (see next section)
D The actuator has been remounted o n a different valve since shipment
D Disassembly of the valve for trim or packing changes
D A new version of firmware has been loaded on the controller
The following scenarios do not require recalibrations
D New unit from the box
D Power dips or interruptions
D Changi ng of control method (i.e. from 420mA to Modbus control)
D Extended periods of storage
Calibration with the use of Modbus
1. After the unit has been properly wired and fused per instructions in the Wiring section of this instruction manual,
turn power to the unit on.
2. Calibrate using Modbus:
a. Send position command of 0% to actuator to prevent unexpected motion. Valve will move to commanded
position following the calibration procedure.
b. Send a value of 1 to register 40003. Valve plug will move to fully closed. The valve plug will then return to the
commanded position.
If a Modbus connection is not available, and recalibration is desired, use the appropriate calibration method as
determined by the control method of your valve.
Calibration without the use of Modbus
1. Turn power to the actuator off