Tuning Procedures
Figure 119: Default Inertia Setting (0)
Figure 120: Inertia Setting (5)
2. Increase the response parameter
The Response is normally the final adjustment when tuning. For best performance the Response should be lower with a higher
inertia mismatch (>10:1) and higher with a lower inertia mismatch.
If your system has some torsional compliance, such as with a jaw type coupling with a rubber spider, or if there is a long drive
shaft, the Response should be decreased. The highest recommended Response with High Performance Gains enabled is 100
Hz.
Also, enabling the Low Pass Filter helps diminish the resonant frequency of torsionally compliant loads. In such cases, using
the Low Pass Filter usually allows for higher Response values. The optimum Low Pass Filter frequency is at the frequency
of the resonance.