Commissioning Assistant
29-10
29.4.10. Base Data - Cell Voltage Screen
Figure 148. Base Data - Cell Voltage (Comm Asst)
Click the Base Data - Cell Voltage button. Data on this screen readily identifies wiring
problems. To save the data, click the Save Voltages button. The voltage data is saved as the
baseline float voltage readings, and the baseline voltages appear in the commissioning report.
29.4.11. Check Float Current Screen
Figure 149. Check Float Current (Comm Asst)
Click the Check Float Current button. Type the float current value in the Measured Value
field, then press <Enter>. If the measured value agrees with the calculated value in the
monitor, the Status area indicates Passed. If the measured value fails, calibrate the monitor to
the measured value by clicking the Cal button.