BDS Diagnostics
27-10
27.11. Resistance Testing Multiple DCM Units
String View > Cell Resistance or Intercell Resistance tab > Diagnostics|R-Test in a DCM
A BDS resistance test checks all the DCM units connected to the BDS. To test a specific
DCM, click the Cell Resistance or Intercell Resistance tab then select R-Test in a DCM. On
the Select DCM box, click the button for the DCM you want to test. To capture new readings,
click OK.
Figure 133. Select DCM
If you clicked OK from Cell Resistance, the screen heading changes to Resistance in DCM n
(Cells n - n) (microhms) and the resistance test starts.
If you clicked OK from Intercell Resistance, the heading changes to Intercell in DCM n
(Cells n - n) (microhms) and the resistance test starts.
After a few minutes, 'test in progress' disappears, and the Get button becomes active. Click
Get to display the readings. The bottom of the screen displays a summary of the resistances
and intertier values measured. To stop the test before completion, click Stop.
Diagnostics does not transfer resistance readings to the permanent database. Be certain to
record the needed results before closing these screens.