Commissioning Assistant
29-9
29.4.8. Check Overall Voltage Screen
Figure 146. Check Overall Voltage (Comm Asst)
Click the Check Overall Voltage button. (Not used with BDS-40.) Measure the overall
voltage, type the value in the Measured Value field, then press <Enter>. If the measured
value agrees with the calculated value in the monitor, the Status area indicates Passed. If the
measured value fails, calibrate the monitor to the measured value by clicking the Cal button.
29.4.9. Check Intertier Screen
Figure 147. Check Intertier (Comm Asst)
Click the Check Intertier button. Measure the intertier voltage, type the value in the
Measured Value field, then press <Enter>. If the measured value agrees with the calculated
value in the monitor, the Status area indicates Passed. The list dynamically changes to show
all intertiers and charger cables. You only have to verify one intertier per DCM. If the
measured value fails, calibrate the monitor to the measured value by clicking the Cal button.