26
Figure 3.33 Suction Group Setup Screen
The E2 will default to a (Board / Point) application.
Before proofing can be programmed the E2 must be
changed to accept a (Controller / Application / Output)
format by following these steps:
1. With the cell next to CMP RUN PROOF highlight-
ed, press F3 (Edit).
2. Press 1 to select Alternate I/O Formats.
3. Press 2 to select Controller / Application /
Property.
4. Input the appropriate Controller / Application /
Property using F4 (Lookup).
Once the proofing associations have been made, the
suction group setup screen should look like figure
3.34 below:
Figure 3.34 Run Proofing Setup Screen
4. Compressor Status Codes
The LED on the Intelligent Store™ Discus® front box
is designed to provide a rapid assessment of the
compressor’s operation condition. The LED codes
also provide some basic diagnostics to aid
troubleshooting of the system or compressor.
• Steady Code (not flashing): An indication of nor-
mal operation. There are no faults or issues with
the compressor.
• Flashing Code (a continuously flashing status
code): Refer to the status code table for interpre-
tation of the fault.
• Flashing of Random Symbols: Occurs for 30 sec-
onds after module power has been turned on. Also
occurs after “Reset” button is pushed. The
sequence of numbers will be an “8” followed by
the node and subnet address for the compressor.
This is normal, and is not an indication of fault.
4.0 Definitions
• Trip: The module has shut off the compressor due
to the fault condition. The compressor will be
available to run when the fault condition no longer
exists, and the minimum off time has been satis-
fied. The reset button does not need to be pushed
to clear a “Trip.” Pushing the reset button will not
clear the trip if the fault condition still exists.
• Lockout: The module has shut off the compressor
due to a fault condition. The compressor will NOT
be available to run when the fault condition has
been cleared until the reset button has been
pushed, or a remote reset has been activated.
4.1 Status Code Descriptions
Here is a brief description of each code that the
Intelligent Store™ Discus® can display, and what the
specific code means.
Steady
Description
0 Normal - Off. The contactor is de-ener-
gized, and the rack controller has not
called for the compressor to run.
1 Normal - Running. The rack controller has
called for the compressor to run, and the
contactor is energized.
2 Normal - Demand Cooling Injecting. The
liquid injection valve has been activated.
• The Discharge Temperature Probe
senses a head temperature above the
injection cut-in temperature, and the
compressor is running.