Specifications
43
Table 14 Liebert XDV specifications
Number of models 8, based on input voltage, optional condensate sensing and flex hose
option
Cooling capacity, nominal
8 kW / 2.2 Tons 6.5 kW / 1.85 Tons
Each capacity is based on 55ºF Entering Coolant Temperature, 92ºF
Entering Air Temperature, 50ºF or lower dew point, rear inlet.
Electrical requirements
Input 120V model: 1ph-60 Hz 230V model: 1ph-50 Hz
Input power connections 120V model: 2 power connections 230V model: 2 power connections
Full Load Amps 120V model: 2.0 A 230V model: 1.0 A
Power consumption, nominal 200 Watts 200 Watts
Dimensions, inches (mm)
Height – unit only 14-1/8 (359) not including pipe connections
Height – including pipe connections 18-7/8 (479)
Width 23-1/2 (597)
Depth – Top 39-3/4 (1010)
Depth – Bottom 29-3/4 (756)
Weight, lb (kg)
Unit only 77 (35)
Shipping weight 125 (57) 136 (62)
Installed, with coolant 79 (36)
Number of fans 2
Airflow, nominal, ft
3
/min (m
3
/hr)
1000 (1699) with rear inlet.
Bottom inlet airflow may be less,
depending on restrictions inside
cabinet.
833 (1415) with rear inlet. Bottom
inlet airflow may be less,
depending on restrictions inside
cabinet.
Audible noise 78 dBa sound power
Pipe connections
XD Coolant supply from XDP/XDChiller 1/2" OD, Cu, (optional 1/2" threaded coupler flex hose)
XD Coolant return to XDP/XDChiller 5/8" OD, Cu, (optional 3/4" threaded coupler flex hose)
Serviceable parts Fans and electrical components
Cabinet exterior finish Black, matte finish, heat-fused powder coat
Options
Condensate sensing (factory-installed) Dry contact outgoing signal
Agency
Safety CSA None
Seitenansicht 48