XD Overhead Cooling Module—Liebert XDO
24
Figure 24 XDO top and front electrical access points
4.1 Liebert XD Vertical Top Cooler (XDV)
4.1.1 Standard Features Liebert XDV
Micro Channel Heat Exchanger—The Liebert XDV unit includes one all-aluminum micro channel
heat exchanger.
Dual IEC Power Cords and Power Inlets—The Liebert XDV unit is supplied with two (2) detach-
able 10 ft (3m) power cords that attach to two (2) IEC power inlets in the rear of the unit. Each
power cord has a NEMA 5-15P (IEC 320-C14) plug at the opposite end.
This feature allows the unit to be powered by two separate power sources.
Dual Air Inlets—The Liebert XDV unit can be configured to allow air to enter from the rear grille
or the bottom of the unit.
Dual Fans—Airflow is provided by two fans on the front of the unit. Dual switches—Controls on
the front of the unit permit the use of one fan or both fans.
Foundation Mounting—There are two 1/4-20 cage nuts located on the underside of unit which
allow direct attachment to any Liebert Foundation cabinet, bolts provided with XDV unit.
Mounting Clips for non-Liebert cabinets—The Liebert XDV unit is supplied with mounting clips
that allow attachment to a non-Liebert cabinet (Some drilling maybe required).
Mounting
Hole
Mounting
Hole
TOP OF XDO
FRONT OF XDO
Knockouts
for High-Voltage
Wiring
Knockouts
for Low-Voltage
Wiring
The low-voltage connection is present only
if the XDO is equipped with the optional
condensation detection system.